UK trade guideBoiler Spares 5 min readUpdated 11 July 2026

How to Replace the Diverter Valve on a Baxi EcoBlue Advance 28 (UK)

Step-by-step UK guide to replacing the 3-way diverter valve on a Baxi EcoBlue Advance 28. Part numbers, torques, commissioning.

Baxi

The part

Replace the diverter valve on Baxi EcoBlue Advance 28 when hot water runs cold on demand or the boiler cycles between CH and DHW.

Isolate safely

Drain to below the diverter body via the CH drain-off. On Baxi EcoBlue Advance 28 the diverter is a cartridge design — pull the retaining clip and lift out.

Fit and commission

Fit new O-rings, silicone-grease the cartridge and align the actuator drive slot before refitting the motor.

Recommission checklist

Refill the Baxi EcoBlue Advance 28 to 1.2 bar cold. Bleed high-point radiators and the internal AAV.

Run a full flue-gas analysis after 15 minutes. Log the reading against the OEM commissioning envelope in the Benchmark book.

Frequently asked questions

Actuator or cartridge only?
Diagnose first: manually push the actuator pin. If it moves freely, replace the actuator only; if the pin sticks, the cartridge is scaled.
Any special tools?
A brass spanner or the OEM diverter tool avoids cracking the plastic body on Baxi EcoBlue Advance 28.
Do I need to notify the manufacturer?
Only if the Baxi EcoBlue Advance 28 is in warranty — Baxi require log of any part swap for labour claims.
Shop the spares

Browse boiler spares14,820 live parts.

View Boiler Spares