How to Replace a Boiler Expansion Vessel (UK Guide)
Replace or recharge a failed expansion vessel on Worcester, Vaillant, Baxi and Ideal combis. Sizing and pre-charge pressures.
Worcester BoschVaillantBaxiIdealZilmet
Diagnose vessel failure
Depress the Schrader valve on the vessel — if water squirts out, the diaphragm has burst and it must be replaced. If only air escapes but pressure still climbs when heating, the pre-charge is low: recharge to 0.75–1.0 bar cold.
Sizing
Most UK combis ship with an 8 L vessel — undersized for systems over 100 L. Fit an external 12 L or 18 L in-line vessel on larger properties.
- 8 L — up to 100 L system volume.
- 12 L — 100–150 L (typical 3-bed house with 10 rads).
- 18 L — 150–200 L, larger unvented + heating combined.
Refit procedure
Isolate flow/return, drain to zero on the gauge, unclip the vessel, transfer the flexible hose. Charge to 0.75 bar with a foot pump before refilling the system to 1.2 bar.
Frequently asked questions
- Can I fit an external vessel instead of pulling the boiler apart?
- Yes — an inline vessel on the return works identically. Faster job, no fascia strip.